Sort: Switchgear sets
(I) Product overview:
KYN44A-12 (Z) type metal armored removable switchgear (switchgear) is a new product developed by Chengdu Mellon Electric Co., Ltd. on the basis of KYN28-12 and absorbing advanced manufacturing technology at home and abroad. The appearance and size are the same as the KYN28-12.
(II) Technical parameters
|
Rated voltage kV |
12 |
|
Rated frequency Hz |
50(60) |
|
Rated short-time power frequency withstand voltage (phase-to-phase, ground) kV |
42 |
|
Rated lightning impulse withstand voltage (phase-to-ground) kV |
75 |
|
Rated short-circuit breaking current (max.) kA |
25~50 |
|
Rated short-circuit closing current (max.) kA |
63~125 |
|
4S rated short-time withstand current (kA) |
25~50 |
|
Rated peak withstand current (kA) |
63~125 |
|
Rated busbar current (max.) A |
630~4000A |
|
Degree of protection (standard) |
IP4X |
|
Note: When the rated current is 4000A, forced air cooling is required. |
|
(iii) Technical advantages of KYN44A-12(Z)
|
Shape size (width × depth × height) mm |
650(800)× 1500 × 2300 (below 1250A) |
|
1000 × 1500 × 2300 (below 4000A) |
|
|
800(1000)× 1660 × 2300 rear overhead |
Through full type test, in line with IEC2771, GB3906, DL404 and many other domestic and international standards and norms
Modular structure, each compartment has an independent pressure release channel (high pressure chamber, bus bar chamber, cable chamber and low pressure chamber can be replaced separately)
The steel plate between each compartment can withstand the gas pressure generated by internal arc fault, and the internal arc of the switch cabinet meets IAC A FLR standard
All operations must be carried out with the high-pressure chamber door closed. The high-pressure chamber door is equipped with a reliable interlocking mechanism.
Reliable "five-proof" mechanical interlocking mechanism
Separate high altitude type tests at an altitude of 3000m.
Through the complete seismic test
(IV) Application Areas
KYN44A-12 (Z) type metal armored removable switchgear (switchgear) is used in substations and power distribution systems, mainly for 7.2-12kV primary power distribution systems.
Petroleum, chemical, metallurgy, machinery, textile, pharmaceutical industry
Rail transit, water supply and sewage treatment works
power supply company
High-rise buildings, commercial buildings, hospitals, scientific research institutions